Superconducting Fault Current Limiter / 13.2kV/630A HTS FCL Cryostat
Cryogenic Equipment > Superconducting power device > Superconducting Fault Current Limiter
Purpose : For for 13.2kV/630A HTS Current Limiter
Technical Features : Subcooled by AL300 cryocooler.
– Cryostat Diameter : 1300 mm
Height : 2093 mm
– LN2 Volume : 1700 ltrs
– Operating Pressure : 6 bar
– Operating Temp : 65 K
– Cooling Capacity : 300 W @ 80K
– Heat Loss : 110 W
Code No. : M0629
Customer : Hyundai Heavy Industries
Delivery : 2006. 12. 11